FREE delivery on orders over €150
Product Specifications:
| Item | Circuit Breaker |
| Ac Voltage Rating | 690V AC |
| Ambient Air Temp. For Operation | -13°F to +158°F |
| Ambient Air Temp. For Storage | -58°F to +185°F |
| Amps | 100A |
| Awg Gauge | 6 AWG to 2/0 AWG, 14 AWG to 3/0 AWG |
| Breaking Capacity | 100 kA 208Y/120V AC 50/60 Hz UL 489, 100 kA 240V AC 50/60 Hz UL 489, 65 kA 480/277V AC 50/60 Hz UL 489, 65 kA 480V AC 50/60 Hz UL 489, 25 kA 600Y/347V AC 50/60 Hz UL 489, 50 kA 250V DC UL 489 |
| Breaking Capacity Code | J |
| Circuit Breaker Actuator | Toggle |
| Circuit Breaker Application | HACR Rated |
| Circuit Breaker Mounting Style | Unit Mount |
| Circuit Breaker Type | Standard |
| Color | Gray |
| Component Type | Circuit Breaker |
| Connection Pitch | 1.06" |
| Continuous Amps Rating | 80% |
| Control Type | Toggle |
| Dc Voltage Rating | Not Rated |
| Depth | 3.15" |
| Device Application | Distribution |
| Electrical Connection | Everlink Lug, Line, Load |
| Electrical Durability | 10000 Cycles |
| For Use With | Electrical Distribution Equipment, Industrial Control Panels |
| Frame Size | 125A/BJ |
| Frame Type | BJL |
| Height | 5.39" |
| Ik Degree Of Protection | IK07 |
| Instantaneous Trip | Fixed |
| Ip Degree Of Protection | IP40 |
| Line Rated Amps | 100A |
| Local Signalling | Presence Of Auxiliary Contacts Flag Green |
| Max. Operating Temp. | 158°F |
| Maximum Air Rating | 100 Ka @ 120/240V Ac |
| Maximum Wire Size | 2 AWG, 3 AWG |
| Mechanical Durability | 20000 Cycles |
| Min. Operating Temp. | -13°F |
| Minimum Wire Size | 14 AWG, 6 AWG |
| Mounting Mode | Clip On 35 mm x 15 mm Symmetrical Din Rail, By Screws Plate |
| Network Frequency | 50/60 Hz |
| No. Of 9 Mm Pitches | 9 |
| No. Of Poles | 3 |
| Number Of Poles | 3 |
| Number Of Slots | 3 |
| Operating Altitude | 0 ft. to 6561.68 ft. Without Derating, 5000m With Derating |
| Phase | Three |
| Phase Connection | ABC |
| Pollution Degree | 3 IEC 60947-1 |
| Power Wire Stripping Length | 0.8" |
| Quality Labels | ce.png |
| Quantity Per Set | Set of 1 |
| Rated Impulse Withstand Voltage | 8 kV |
| Rated Insulation Voltage | 800V |
| Rated Operational Voltage | 690V |
| Rated Service Breaking Capacity | 100 kA @ 220-240V AC @ 50/60 Hz, 25 kA @ 500-525V AC @ 50/60 Hz, 10 kA @ 690V AC @ 50/60 Hz, 65 kA @ 380-415V AC @ 50/60 Hz, 65 kA @ 440V AC @ 50/60 Hz |
| Returnability | Yes |
| Suitability For Isolation | Yes, IEC 60947-2 |
| Terminal Connection | Everlink Lug Both Ends |
| Tightening Torque | 44.3 lbf.in. @ 0.004 sq. in. to 0.02 sq. in. @ 14 AWG to 4 AWG, 79.7 lbf.in. @ 0.04 sq. in. to 0.1 sq. in. @ 3 AWG to 3/0 AWG |
| Trip Type | Thermal Magnetic |
| Trip Unit Technology | Thermal-Magnetic |
| Utilisation Category | Category A |
| Voltage | 600V |
| Voltage Type | AC |
| Width | 3.19" |
Shipping Info:
| Ship weight (kg) | 1.31 |
| Ship height (cm) | 13.69 |
| Ship length (cm) | 8 |
| Ship width (cm) | 8.1 |
| Country of Origin | MX |
Product Details:
- Square D BJL36100 molded case circuit breaker designed to protect electronic equipment from short-circuit and overload conditions
- Non-interchangeable thermal magnetic trip offers both long-time and instantaneous trip functions, suitable for reverse feed applications
- 3 pole unit featuring patented EverLink lug connections on both line and load ends for easy service and repairs
- Comes equipped with dual-break rotating contacts which reduce the amount of peak current during a short circuit fault
Product Variants
| Model | Amps | Circuit Breaker Type | Frame Size | Number Of Poles | Ac Voltage Rating | Phase | Phase Connection | Voltage Type | Price | |
|---|---|---|---|---|---|---|---|---|---|---|
| BJL36015 | 15A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €1,599.20 | |
| BJL36090 | 90A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €2,020.04 | |
| BJL36060 | 60A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €1,599.20 | |
| BJL36080 | 80A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €2,020.04 | |
| BJL36070 | 70A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €2,020.04 | |
| BJL36040 | 40A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €1,599.20 | |
| BJL36030 | 30A | Standard | 125A/BJ | 3 | 690V AC | Three | ABC | AC | €1,599.20 |
Explore Products
- PEER CHAIN 785 Roller Chain, C2060 Stainless Pitch, 100 Feet Length
- TITAN FASTENERS CGP03104FT
- MAIN FILTER INC. MF0061614 DVD2140E10V Interchange Hydraulic Filter, Glass, 10 Micron, Viton Seal, 5.98 Inch Height
- MARTIN SPROCKET 458 Pin Spanner Wrench, SAE, 2 1/2 Inch Size, Industrial Black, Steel
- JACOBS CHUCK 5514 5514D
- GEARENCH SG1000-10L
- EATON HMX3D4C4NAPEP3L3SA Adjustable Frequency Drive, 3.4A, 2HP, Space Heater With Transformer, NEMA 3R, FS4, 480V
- DYNABRADE 58022 Non-Vacuum Backsplash Radius Disc Pad, 1/2 Inch Size
Explore More
- APW WYOTT
- FLEXIDUCT
- KEYSHAFT
- INA
- TECHNIKS
- Press Fit Fittings
- Flow Rate Sensors
- Cord Adapters
- Solar Panels
- UV Systems
- KRYTOX XHT-1000 Series Extreme High Temperature PFPE Oil
- BURNDY AMS Dual Rated Splicers/Reducers
- ANVIL AS1100 Series Rigid Steel Conduit Clamps, Zinc Trivalent Chromium
- ANVIL AS300BTB Series Welded Channels
- COOPER B-LINE Flat Gusset Tee Plates
- EATON 50 Series Polarized Reflex Sensors
- ZURN Tubings
- DWYER INSTRUMENTS Digital Manometers
- NIBCO TS-595-Y Series Three-Piece Bronze Ball Valves, Thread x Solder End Connection
Contact us
Contact your account manager right away to get personal advice.
We're available Monday through Friday, from 07:30 until 17:00.
SQUARE D BJL36100 PowerPact B Circuit Breaker, 100 A, 3 Poles, Thermal Magnetic