SQUARE D HLA260704 Molded Case Circuit Breaker, 70A, 2 Poles, 50kA@600VAC
70A
2
Get it by Monday, Aug 24
Request a Quote
Payment
Delivery
Product Specifications:
| Item | Circuit Breaker |
| Ambient Air Temp. For Operation | -13°F to +158°F |
| Ambient Air Temp. For Storage | -58°F to +185°F |
| Amps | 70A |
| Awg Gauge | 14 AWG to 3/0 AWG |
| Breaking Capacity | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 |
| Breaking Capacity Code | L |
| Circuit Breaker Application | HACR Rated |
| Color | Black |
| Communication Interface | Modbus, Ethernet |
| Component Type | Circuit Breaker |
| Continuous Amps | 80% |
| Control Type | Toggle |
| Depth | 3.4" |
| Device Application | Distribution |
| Electrical Connection | I-Line Connection, Line, Lugs, Load |
| Frame Type | HLA |
| Height | 6 2/5" |
| Ip Degree Of Protection | IP40 |
| Line Rated Amps | 70A |
| Local Signalling | Switched Off 1 Trip Indicator Green |
| Magnetic Hold Amps | 800A |
| Magnetic Tripping Amps | 1450A |
| Mounting Height | 4.5" |
| Mounting Mode | I Line Bracket |
| Mounting Support | Bracket |
| Network Frequency | 50/60 Hz |
| No. Of Poles | 2 |
| No. Of Slots | 5 |
| Operating Altitude | 0 ft. to 6561.68 ft. Without Derating, 5000m With Derating |
| Phase Connection | BC |
| Pollution Degree | 3 IEC 60947-1 |
| Power Wire Stripping Length | 0.6" |
| Quality Labels | ce.png |
| Quantity Per Set | 1 |
| Rated Impulse Withstand Voltage | 8 kV |
| Rated Insulation Voltage | 750V |
| Rated Operational Voltage | 690V |
| Rated Service Breaking Capacity | 125 kA @ 220/240V AC @ 50/60 Hz, 100 kA @ 380/440/415V AC @ 50/60 Hz, 50 kA @ 500/525V AC @ 50/60 Hz, 20 kA @ 250V DC, 20 kA @ 500V DC |
| Returnability | No |
| Suitability For Isolation | Yes, IEC 60947-2 |
| Tightening Torque | 44.3 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 123.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 3/0 AWG |
| Trip Unit Technology | Thermal-Magnetic |
| Utilisation Category | Category A |
| Voltage | 600V |
| Voltage Type | AC |
| Width | 4.09" |
Shipping Info:
| Ship weight (kg) | 1.8 |
| Ship height (cm) | 13.67 |
| Ship length (cm) | 37.16 |
| Ship width (cm) | 20.65 |
| Country of Origin | US |
Product Details:
- Square D HLA260704 HLA Series circuit breaker used in high load intensity equipment for protection against electrical hazards
- Features unique I-Line mounting with lug load connection for easy installation and repairs
- Long-time & instantaneous trip functions for responding against severe short-circuits instantaneously while avoiding tripping on mild overloads, suitable for reverse feed applications
- Supports copper and aluminium wires of sizes from 14 to 3/0 AWG
- CSA certified and CCC / IEC approved
Product Variants
| Model | No. Of Poles | Amps | Phase Connection | Line Rated Amps | Breaking Capacity | Returnability | Magnetic Tripping Amps | Magnetic Hold Amps | Price | |
|---|---|---|---|---|---|---|---|---|---|---|
| HLA260351 | 2 | - | AB | 35A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | No | 850A | 400A | €1,296.00 | |
| HLA260352 | 2 | - | AC | 35A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | Yes | 850A | 400A | €1,296.00 | |
| HLA260354 | 2 | - | BC | 35A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | Yes | 850A | 400A | €1,296.00 | |
| HLA260802 | 2 | - | AC | 80A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | Yes | 1450A | 800A | €1,611.00 | |
| HLA260804 | 2 | - | BC | 80A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | Yes | 1450A | 800A | €1,611.00 | |
| HLA260901 | 2 | - | AB | 90A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | No | 1450A | 800A | €1,611.00 | |
| HLA260902 | 2 | - | AC | 90A | 125 kA 240V AC 50/60 Hz UL 489, 100 kA 480V AC 50/60 Hz UL 489, 50 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 50 kA 500V DC UL 489 | No | 1450A | 800A | €1,611.00 |
Explore Products
- LIFT-ALL 932TASAM10X24 9/32 Inch Tasa x 24 Ft. Mech Triple Adj Sling Hook Style A G100 Chain Sling
- SMC VALVES MHZAJ2-6S Air Gripper
- SLOAN 3850811 Sink, 2 Station
- USA SEALING BULK-CR-GFR4-58 Rod Stock, Garolite, 9/16 Inch Diameter
- OSG HP419-0394 Ball End Mill, 2 Flutes, 1 mm Milling Dia., 1 mm Lg Of Cut, 5.00 mm Neck Lg, TiAlN
- TECHNIKS 22729-4 Face Mill Holder, 4 Inch Projection
- 3M 7100138158 60440201188 / 40220 Spiral Band, 3/4 Inch Dia, 80 Grit
- CLEVELAND C95104 Carbide Thread Mill, AlCrN, 3 Flute, #2-56/#3-56 Thread Size, 0.1970 Inch Length
Explore More
- KEYSHAFT
- LEATHERHEAD TOOLS
- NEW PIG
- POWER DRIVE
- R B FABRICATIONS
- Bathroom Sinks
- Signal Conditioner
- Gas Detector Battery Chargers
- Sight Plugs
- Steam Fittings
- MILLER ELECTRIC TIG/MIG Task Welding Gloves
- ANSELL Class 00 Electrical Gloves, 14 Inch, Black
- ANSELL Class 2 Electrical Gloves, 16 Inch, Yellow
- MUELLER INDUSTRIES 782 Stainless Steel Y Strainers
- ANVIL 212 Series Medium Pipe Clamps, Stainless Steel
- FEIN POWER TOOLS Fleece Disc Abrasive
- APPROVED VENDOR M16 x 2 Fully Threaded Standard Hex Black Oxide Alloy Steel Flat Machine Screws
- INSIZE Linear Scales for Digital Readouts
- TENACTIV Knit Cold Condition Insulated Gloves
- BRISKHEAT KM Series Constant Heating Cables
Contact us
Contact your account manager right away to get personal advice.
We're available Monday through Friday, from 07:30 until 17:00.
SQUARE D HLA260704 Molded Case Circuit Breaker, 70A, 2 Poles, 50kA@600VAC