Product Specifications:

Item Circuit Breaker
Ac Voltage Rating 600V AC
Actuator Toggle
Actuator Type Toggle
Ambient Air Temp. For Operation -13°F to +158°F
Ambient Air Temp. For Storage -58°F to +185°F
Amps 100A
Awg Gauge 14 AWG to 3/0 AWG
Breaking Capacity 65 kA 240V AC 50/60 Hz UL 489, 35 kA 480V AC 50/60 Hz UL 489, 18 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 20 kA 500V DC UL 489
Breaking Capacity Code G
Circuit Breaker Actuator Toggle
Circuit Breaker Application HACR Rated
Circuit Breaker Mounting Style Free Standing
Circuit Breaker Type Standard
Color Black
Communication Interface Modbus, Ethernet
Component Type Circuit Breaker
Continuous Amps Rating 80%
Control Type Toggle
Dc Voltage 250V DC
Dc Voltage Rating 250/500V DC
Depth 3.4" , 4.36"
Device Application Distribution
Electrical Connection Lugs, Line, Load
Frame Size 150A/HG
Frequency 50/60 Hz
Height 6 2/5"
High Amp Trip Setting 1700A
Instantaneous Trip Fixed
Ip Degree Of Protection IP40
Line Rated Amps 100A
Local Signalling Switched Off 1 Trip Indicator Green
Low Amp Trip Setting 900A
Magnetic Hold Amps 900A
Magnetic Hold Current 900A
Magnetic Tripping Amps 1700A
Magnetic Tripping Current 1700A
Max. Air Rating Not Rated
Max. Air Rating 65 kA At 240V AC
Max. Breaking Capacity 65 kA @ 240V AC
Max. Operating Temp. 104°F
Max. Wire Size 3 AWG
Min. Wire Size 14 AWG
Mounting Free Standing
Mounting Mode Unit Mount Lug
Mounting Style Free Standing
Mounting Support Lug
Network Frequency 50/60 Hz
No. Of Poles 3
Number Of Poles 3
Number Of Slots 5
Operating Altitude 0 ft. to 6561.68 ft. Without Derating, 5000m With Derating
Phase 3
Phase Connection ABC
Pollution Degree 3 IEC 60947-1
Power Wire Stripping Length 0.6"
Product Datasheet square-d-al250jd.pdf
Quality Labels ce.png
Quantity Per Set 1
Rated Impulse Withstand Voltage 8 kV
Rated Insulation Voltage 750V
Rated Operational Voltage 690V
Rated Service Breaking Capacity 65 kA @ 220/240V AC @ 50/60 Hz, 35 kA @ 380/440/415V AC @ 50/60 Hz, 18 kA @ 500/525V AC @ 50/60 Hz, 20 kA @ 250V DC, 20 kA @ 500V DC
Returnability Yes
Series HG Series
Suitability For Isolation Yes, IEC 60947-2
Terminal Connection Line/Load Lug
Terminal Connection Type Line, Load Lug
Tightening Torque 44.3 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 123.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 3/0 AWG
Trip Type Thermal Magnetic
Trip Unit Technology Thermal-Magnetic
Utilisation Category Category A
Width 4.09" , 4.12"

Shipping Info:

Ship weight (kg) 1.86
Ship height (cm)18.8
Ship length (cm)22.35
Ship width (cm)16.51
HS code8536200020
Country of OriginMX

Product Details:

Square D HGL36100 circuit breaker is suitable to protect electrical systems from damage caused by overloads and short circuits. This PowerPacT circuit breaker is used in electrical distribution panels, motor control centres and power distribution units.

Features:

  • It is equipped with dual-break rotating contacts for reducing the peak current during a short circuit condition, allowing equipment safety.
  • This PowerPacT breaker switch has an integral push-to-trip button in the cover for manual trip function.
  • It has lugs on both the line and load sides, allowing quick and easy installation.
  • This circuit breaker has an interrupt rating of 18kA at 600VAC.

Frequently Asked Questions:

Q. What is the operating temperature range of Square D HGL36100 circuit breaker?

A. It has an operating temperature range of 28 to 158 degrees F.

Q. What are the factors to consider for safely installing this Square D HGL36100 circuit breaker?

A. It is important to follow safety guidelines during installation, such as working in de-energized environments, using appropriate personal protective equipment (PPE) and following lockout / tagout procedures. Mount the circuit breaker onto a compatible panel, connecting the necessary wiring and ensuring proper torque settings for terminal connections.

Q. Can Square D HGL36100 be used in combination with other circuit protection devices?

A. Yes, it can be used with other protective devices like relays, fuses and surge protectors to enhance overall system protection.

Q. How do I maintain this HGL36100 circuit breaker?

A. Routine visual inspections are recommended to check for any signs of damage, overheating or wear. In dusty environments, periodic cleaning might also be necessary.

Documentation:

Datasheet

Product Variants

ProductModelNumber Of PolesAmpsPhaseTerminal Connection TypeHigh Amp Trip SettingLow Amp Trip SettingDc Voltage RatingTerminal ConnectionPrice
SQUARE D HGL36150U33X Circuit Breaker 150a 3 Pole 600vac Box Lug | AF6GCN 14G974 HGL36150U33X3150A3Box Lug100A150A250V ACBox Lug€3,030.01
SQUARE D HGL36060U43X Circuit Breaker 60a 3 Pole 600vac Box Lug | AF6GCP 14G975 HGL36060U43X360A3Box Lug15A60A250V ACBox Lug€4,904.63
SQUARE D HGL36100U43X Circuit Breaker 100a 3 Pole 600vac Box Lug | AF6GCQ 14G976 HGL36100U43X3100A3Box Lug60A100A250V ACBox Lug€5,160.90
SQUARE D HGL36150U43X Circuit Breaker 150a 3 Pole 600vac Box Lug | AF6GCR 14G977 HGL36150U43X3150A3Box Lug100A150A250V ACBox Lug€8,493.42
SQUARE D HGL36060U31X Circuit Breaker 60a 3 Pole 600vac Box Lug | AF6GCT 14G969 HGL36060U31X360A3Box Lug15A60A250V ACBox Lug€1,413.97
SQUARE D HGL36100U31X Circuit Breaker 100a 3 Pole 600vac Box Lug | AF6GCU 14G970 HGL36100U31X3100A3Box Lug60A100A250V ACBox Lug€3,104.85
SQUARE D HGL36150U31X Circuit Breaker 150a 3 Pole 600vac Box Lug | AF6GCV 14G971 HGL36150U31X3150A3Box Lug100A150A250V ACBox Lug€6,544.68

Contact us

Contact your account manager right away to get personal advice.
We're available Monday through Friday, from 07:30 until 17:00.

SQUARE D HGL36100 Circuit Breaker, 100A, 3 Pole, 600VAC, 18KA, Lugs, Thermal Magnetic
€1,321.45 /unit