DWYER INSTRUMENTS 616KD Series Differential Pressure Transmitters
Dwyer 616KD Series differential pressure transmitters are designed to measure the difference in pressure between two points in a system and convert that measurement into an electrical signal for further processing or control.
Filter
| Style | Model | Max. Pressure | Over Pressure | Pressure | Output | No. Of Wires | No. Of Wire | Power Required | Operating | Price | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| A | 616KD-03-V | - | 2 psig | 0 in. wc to 5 in. wc | - | - | - | - | - | €172.20 | |
| A | 616KD-02-V | - | 2 psig | 0 in. wc to 3 in. wc | - | - | - | - | - | €170.54 | |
| A | 616KD-01 | - | 2 psig | 0 in. wc to 2 in. wc | 4-20 mA | - | - | 16-35V DC | - | €212.74 | |
| A | 616KD-00-V | 1 in. wc | 2 psig | 0 in. wc to 1 in. wc | 0-10V DC/0-5V DC | 2, 3, 4 | - | 10-35V DC (5V 3 Wire), 16-36V DC (10V 2 Or 3 Wire), 12-26V AC (5V 4 Wire), 20-28V AC (10V 3 Wire) | - | €170.49 | |
| A | 616KD-00 | 1 in. wc | 2 psig | 0 in. wc to 1 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | - | €207.28 | |
| A | 616KD-01-V | 2 in. wc | 2 psig | 0 in. wc to 2 in. wc | 0-10V DC/0-5V DC | 2, 3, 4 | - | 10-35V DC (5V 3 Wire), 16-36V DC (10V 2 Or 3 Wire), 12-26V AC (5V 4 Wire), 20-28V AC (10V 3 Wire) | - | €162.88 | |
| A | 616KD-02 | 3 in. wc | 2 psig | 0 in. wc to 3 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | - | €191.62 | |
| A | 616KD-03 | 5 in. wc | 2 psig | 0 in. wc to 5 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | - | €212.74 | |
| A | 616KD-05 | 5 psig | 5 psig | 0 in. wc to 15 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | 0 in. wc to 15 in. wc | €181.18 | |
| A | 616KD-07 | 5 psig | 5 psig | 0 in. wc to 25 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | 0 in. wc to 25 in. wc | €182.53 | |
| A | 616KD-06 | 5 psig | 5 psig | 0 in. wc to 20 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | 0 in. wc to 20 in. wc | €178.23 | |
| A | 616KD-04 | 10 in. wc | 5 psig | 0 in. wc to 10 in. wc | 4-20 mA | 2, 4 | 10-35V DC/12-26V AC | - | - | €192.07 | |
| A | 616KD-05-V | 15 in. wc | 5 psig | 0 in. wc to 15 in. wc | 0-10V DC/0-5V DC | 2, 3, 4 | - | 10-35V DC (5V 3 Wire), 16-36V DC (10V 2 Or 3 Wire), 12-26V AC (5V 4 Wire), 20-28V AC (10V 3 Wire) | - | €153.48 | |
| A | 616KD-06-V | 20 in. wc | 5 psig | 0 in. wc to 20 in. wc | 0-10V DC/0-5V DC | 2, 3, 4 | - | 10-35V DC (5V 3 Wire), 16-36V DC (10V 2 Or 3 Wire), 12-26V AC (5V 4 Wire), 20-28V AC (10V 3 Wire) | - | - | RFQ
|
| A | 616KD-07-V | 25 in. wc | 5 psig | 0 in. wc to 25 in. wc | 0-10V DC/0-5V DC | 2, 3, 4 | - | 10-35V DC (5V 3 Wire), 16-36V DC (10V 2 Or 3 Wire), 12-26V AC (5V 4 Wire), 20-28V AC (10V 3 Wire) | - | - | RFQ
|
Working Mechanism
- Differential pressure transmitters are devices used to measure the difference in pressure between two points in a fluid or gas system. They consist of a sensing element, typically a diaphragm or a set of diaphragms, which are exposed to the pressure inputs.
- The high-pressure input is connected to one side of the sensing element, while the low-pressure input is connected to the other side. The pressure difference causes a displacement or deflection of the sensing element.
- This displacement is converted into a mechanical or electrical signal through mechanisms like strain gauges, capacitance, or piezoelectric materials. The converted signal is then processed and amplified to generate an output signal.
- This output signal can be measured and interpreted by instruments or control systems to provide accurate and real-time differential pressure measurements, allowing for monitoring, control, and analysis of fluid or gas systems.
Features
- Dwyer 616KD Series differential pressure transmitters can be operated with air and non-combustible gases.
- These differential pressure transmitters have a push button for adjusting both span and zero for enabling fine-tuning of the measurement range according to the application requirements.
- They can be operated at temperatures ranging from 0 to 140 degrees F.
- These Dwyer Instruments 616KD differential pressure transmitters have screw-type terminal blocks for better electrical connections.
- They are equipped with vertical pressure connections pointing down for easy mounting.
Frequently Asked Questions
What is the accuracy of the 616KD Series transmitters?
+/- 2% full scale.
Can Dwyer Instruments 616KD differential pressure transmitters measure both positive and negative pressures?
Yes, the brand's 616KD Series transmitters are capable of measuring both positive and negative pressures. They are designed to provide differential pressure measurements, which means they can measure the pressure difference between two points, regardless of whether the pressures are positive or negative.
How to maintain Dwyer Instruments 616KD differential pressure transmitters?
- Regularly inspect the transmitters for physical damage, loose connections, or leaks, paying attention to pressure and electrical connections.
- Perform periodic calibration to ensure accuracy by adjusting the zero and span settings according to the manufacturer's instructions.
- Keep the transmitters clean by gently wiping the surfaces with a soft cloth or brush, avoiding harsh chemicals.
- Protect the transmitters from environmental factors, such as extreme temperatures or moisture, using weatherproof enclosures or other appropriate measures.
- Check electrical connections for tightness and corrosion, addressing any issues promptly.
We are here to help!
Looking for a part not listed here?
Popular Search Queries
Explore More
- KEYSHAFT
- STRANCO INC
- MALIN CO.
- AUTOQUIP
- USA SEALING
- Drawer Bins
- Electric Polishers And Buffers
- Ceiling Fan Accessories
- Halogen Leak Detector Accessories
- Gasket Sealants And Makers
- AKRO-MILS 30287 Akrobins Super Size Bins
- NORTH BY HONEYWELL NF11 Northflex Nylon Gloves, Red
- IRONCLAD Workcrew Light Duty Gloves
- MUELLER INDUSTRIES LF352 Bronze Body Y Strainers
- ANVIL AS665 Series Four Hole Double Corner Connectors
- JUSTRITE Work Space Guards
- HOFFMAN Filter Grille Panels
- SPEARS VALVES CPVC True Union Ball Check Valves, BSP Threaded, FKM
- MASTER Pneumatic Equipment Parts
- SQUARE D Circuit Breaker Enclosures